Commissioning via the built-in BOP
5.6 Function commissioning
SINAMICS V20 Converter
Operating Instructions, 10/2019, A5E34559884-012
137
Taking the 22 kW SINAMICS converter as an example, when HO mode is selected, it means
the rated power rating is 22 kW; when LO mode is selected, the rated power rating is
changed to 30 kW.
HO mode
Overload capability: 150% of the rated output current for 60 s
Cycle time: 300 s
LO mode:
Overload capability: 110% of the rated output current for 60 s
Cycle time: 300 s
Setting parameter
Parameter
Function
Setting
P0205 Select converter
applications
This parameter selects the converter applications on high overload
and low overload:
=0: high overload
=1: low overload
Function diagram