Communicating with the PLC
7.1 USS communication
SINAMICS V20 Converter
Operating Instructions, 10/2019, A5E34559884-012
177
Request descriptive element
Request parameter value (array)
Modify parameter value (array, word)
Modify parameter value (array, double word)
Request number of array elements
Modify parameter value (array, double word) and store in EEPROM
Modify parameter value (array, word) and store in EEPROM
Modify parameter value (double word) and store in EEPROM
Modify parameter value (word) and store in EEPROM
Response IDs (slave → master)
Transfer parameter value (word)
Transfer parameter value (double word)
Transfer descriptive element
Transfer parameter value (array, word)
Transfer parameter value (array, double word)
Transfer number of array elements
Request cannot be processed, task cannot be executed (with error number)
No master controller status/no parameter change rights for PKW interface
Error numbers in response ID 7 (request cannot be processed)
Illegal PNU (illegal parameter number; parameter number not available)
Parameter value cannot be changed (parameter is read-only)
Lower or upper limit violated (limit exceeded)
Wrong parameter type/incorrect data type
Setting is not allowed (parameter value can only be reset to zero)
7 The descriptive element is not changeable and can only be read
Descriptive data not available
No parameter change rights. See parameter P0927. Must have status as master control.
The current converter operating status does not permit the request processing
20 Illegal value. Change request for a value which is within the limits, but it is not allowed for other reasons (pa-
rameter with defined single values)