Parameter list
8.1 Introduction to parameters
SINAMICS V20 Converter
194 Operating Instructions, 10/2019, A5E34559884-012
For example, copying of all values from CDS0 to CDS2 can be accomplished by the
following procedure:
1. Set P0809[0] = 0: copy from CDS0
2. Set P0809[1] = 2: copy to CDS2
3. Set P0809[2] = 1: start copy
Command data set
The command data sets are changed over using the BICO parameters P0810 and P0811,
whereby the active command data set is displayed in parameter r0050. Changeover is
possible in both the "Ready" and the "Run" states.
P0810 = 0
P0811 = 0
CDS0
P0810 = 1
P0811 = 0
CDS1
P0810 = 0 or 1
P0811 = 1
CDS2
Drive data set
The drive data sets are changed over using the BICO parameters P0820 and P0821,
whereby the active drive data set is displayed in parameter r0051. Drive data sets can only
be changed over in the "Ready" state.
P0820 = 0
P0821 = 0
DDS0
P0820 = 1
P0821 = 0
DDS1
P0820 = 0 or 1
P0821 = 1
DDS2
BI, BO, CI, CO, CO/BO in parameter names
Note
The "Index" chapter at the end of this manual provides groups of the BICO parameters.
Certain parameter names include the following abbreviated prefixes: BI, BO, CI, CO and
CO/BO followed by a colon. These abbreviations have the following meanings:
BI =
Binector input: Parameter selects the source of a binary signal
Each BI parameter can connect as the input to any BO or CO/BO parameter.
BO =
Binector output: Parameter connects as a binary signal
Each BO parameter can connect as the output to any BI parameter.