Parameter list
8.2 Parameter list
SINAMICS V20 Converter
Operating Instructions, 10/2019, A5E34559884-012
199
Defines time period after which the backlight of the operator panel display turns off if no buttons have been
pressed.
Number of seconds after which the backlight turns off.
P0010
0 - 30 0 T - - U16 1
Filters parameters so that only those related to a particular functional group are selected.
Reset to 0 for converter to run.
P0003 (user access level) also determines access to parameters.
• P0010 = 1
The converter can be commissioned very quickly and easily by setting P0010 = 1. After that only the
important parameters (e.g.: P0304, P0305, etc.) are visible. The value of these parameters must be en-
tered one after the other. The end of quick commissioning and the start of internal calculation will be
done by setting P3900 = 1 - 3. Afterwards parameter P0010 and P3900 will be reset to zero automati-
cally.
• P0010 = 2
For service purposes only.
• P0010 = 30
When resetting the parameters or user default values of converter P0010 must be set to 30.
Resetting of the parameters will be started by setting parameter P0970 = 1. The converter will automat-
ically reset all its parameters to their default settings. This can prove beneficial if you experience prob-
lems during parameter setup and wish to start again.
Resetting of the user default values will be started by setting parameter P0970 = 21. The converter will
automatically reset all its parameters to the factory default settings. Duration of factory setting will take
P0011
Lock for user-defined
parameter
0 - 65535 0 U, T - - U16 3
P0012
Key for user-defined
parameter
0 - 65535 0 U, T - - U16 3