Parameter list
8.2 Parameter list
SINAMICS V20 Converter
206 Operating Instructions, 10/2019, A5E34559884-012
r0056.0...15
CO/BO: Status of
motor control
- - - - - U16 3
Displays status of motor control (in bit format), which can be used to diagnose converter status.
Motor demagnetizing finished
Voltage soft start select
Motor excitation finished
Acceleration boost active
f_out > f_max Freq. limited
Imax controller active/torque limit reached
Vdc_max controller active
KIB (Vdc_min control) active
The I-max controller (r0056 bit 13) will be activated when the actual output current (r0027) exceeds the
r0066
CO: Actual output
frequency [Hz]
- - - - - Float 3
Displays actual output frequency in Hz. This value is available filtered (r0024) and unfiltered (r0066).
The output frequency is limited by the values entered in P1080 (minimum frequency) and P1082 (maxi-
r0067
CO: Actual output
current limit [A]
- - - P2002 - Float 3
Displays valid maximum output current of converter.
r0067 is influenced/determined by the following factors:
• Converter application P0205
• Rated motor current P0305
• Motor overload factor P0640
• Motor protection in dependency of P0610
• r0067 is less than or equal to maximum converter current r0209
• Converter protection in dependency of P0290
A reduction of r0067 may indicate a converter overload or a motor overload.
Displays unfiltered [rms] value of motor current. This value is available filtered (r0027) and unfiltered
Used for process control purposes (in contrast to r0027, which is filtered and is used to display the value