Parameter list
8.2 Parameter list
SINAMICS V20 Converter
Operating Instructions, 10/2019, A5E34559884-012
211
Parameter
Function
Range
Factory
default
Can be
changed
Scaling
Data set
Data
type
Acc.
Level
r0206
Rated converter pow-
er [kW]/[hp]
- - - - - Float 2
Displays nominal rated motor power from converter.
Dependency:
Value is displayed in [kW] or [hp] depending on setting for P0100 (operation for Europe/North America).
r0207[0...2]
Rated converter cur-
rent [A]
- - - - - Float 2
Displays rated converter current.
Index:
[0]
Rated converter current
[1]
Rated LO current
[2]
Rated HO current
Note:
The rated high overload (HO) current r0207[2] values correspond to suitable 4-pole Siemens standard
motors (IEC) for the selected load cycle (see diagram). r0207[2] is the default value of P0305 in associa-
tion with the HO application (load cycle).
r0208
Rated converter voltage
[V]
- - - - - U32 2
Displays nominal AC supply voltage of converter.
Note:
r0208 = 230: 200 V to 240 V (tolerance: -10% to +10%)
r0208 = 400: 380 V to 480 V (tolerance: -15% to +10%)