Parameter list
8.2 Parameter list
SINAMICS V20 Converter
214 Operating Instructions, 10/2019, A5E34559884-012
P0292
Converter temperature
warning [°C]
0 - 25 5 U, T - - U16 3
Defines the temperature difference (in °C) between the overtemperature trip threshold (F4) and the warn-
ing threshold (A504) of the converter. The trip threshold is stored internally by the converter and cannot be
2
Defines the [%] value at which warning A505 (converter I
2
t) is generated.
Converter I
2
t calculation is used to determine a maximum tolerable period for converter overload.
2
t calculation value is deemed = 100 % when this maximum tolerable period is reached.
• The output current of the converter has been reduced.
• The value of I
2
t does not exceed 100 %.
P0294 = 100 % corresponds to stationary nominal load.
P0295
Converter fan off delay time
[s]
0 - 3600 0 U, T - - U16 3
Defines converter fan switch-off delay time in seconds after converter has stopped.
Setting to 0, converter fan will switch off when the converter stops, that means no delay.
P0301[0...2]
Easy motor data, rated
motor power [kW]
0 - 2000 0 C(1) - DDS Float 1
Rated motor power from the rating plate. No other data is necessary. If this parameter is used, the rest of
the motor data are then estimated by the firmware.
Changeable only when P0010 = 1 (quick commissioning).
This functionality is only valid with 50 Hz supply, star configuration on 4-pole motors. You must set this
parameter to zero if you desire to set the other motor data.
Nominal motor voltage from rating plate.
Changeable only when P0010 = 1 (quick commissioning).
Default value is depending on converter type and its rating data.
The input of rating plate data must correspond with the wiring of the motor (star/delta). This means, if delta
wiring is used for the motor, delta rating plate data has to be entered.