Parameter list
8.2 Parameter list
SINAMICS V20 Converter
220 Operating Instructions, 10/2019, A5E34559884-012
r0370[0...2]
- - - PERCEN
DDS Float 4
Displays standardized stator resistance of motor equivalent circuit (phase value).
r0372[0...2]
- - - PERCEN
DDS Float 4
Displays standardized cable resistance of motor equivalent circuit (phase value). It is estimated to be 20
% of the stator resistance.
r0373[0...2]
Rated stator resistance [%]
- - - PERCEN
DDS Float 4
Displays rated stator resistance of the motor equivalent circuit (phase value).
r0374[0...2]
- - - PERCEN
DDS Float 4
Displays standardized rotor resistance of the motor equivalent circuit (phase value).
r0376[0...2]
Rated rotor resistance [%]
- - - PERCEN
DDS Float 4
Displays rated rotor resistance of the motor equivalent circuit (phase value).
r0377[0...2]
Total leakage reactance
[%]
- - - PERCEN
DDS Float 4
Displays standardized total leakage reactance of the motor equivalent circuit (phase value).
r0382[0...2]
- - - PERCEN
DDS Float 4
Displays standardized main reactance of the motor equivalent circuit (phase value).
Displays calculated rotor time constant.
r0386[0...2]
Total leakage time constant
[ms]
- - - - DDS Float 4
Displays total leakage time constant of motor.
r0395
CO: Total stator resistance
[%]
- - - PERCEN
- Float 3
Displays stator resistance of motor of combined stator/cable resistance.
P0503[0...2]
Enable Keep-running Op-
eration
0 - 1 0 T - - U16 3
Enables keep-running operation. This attempts to prevent the converter from tripping by enabling all pos-
sible existing de-rating features, and the automatic restart function. May be used with P2113 = 1 (convert-
er warnings disabled) to mask resulting warnings from the user.
Keep-running mode disabled
Keep-running mode enabled