EasyManua.ls Logo

Siemens SINAMICS V20

Siemens SINAMICS V20
426 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Parameter list
8.2 Parameter list
SINAMICS V20 Converter
Operating Instructions, 10/2019, A5E34559884-012
235
Parameter
Function
Range
Factory
default
Can be
changed
Scaling
Data
set
Data
type
Acc.
Level
P0802
Transfer data from
EEPROM
0 - 2 0 C(30) - - U16 3
Transfers values from the converter to external device when P0802 ≠ 0. P0010 must be set to 30 for this
to be possible.
0
Disabled
2
Start data transfer to the SD card
Note:
Parameter is automatically reset to 0 (default) after transfer.
P0010 will be reset to 0 on successful completion.
Ensure that enough space exists on the SD card before transferring data (8 KB).
P0803
Transfer data to
EEPROM
0 - 3 0 C(30) - - U16 3
0
Disabled
2
Start data transfer from the SD card
3
Start data transfer from the SD card (except the motor data)
Transfers parameter values from the SD clone file to the converter when P0803 ≠ 0. P0010 must be set to
30 to activate this parameter. See P0802 for parameter values.
Note:
Parameter is automatically reset to 0 (default) after transfer.
P0010 will be reset to 0 on successful completion.
P0804
Select Clone file
0 - 99
0
C(30)
-
-
U16
3
Select clone file to upload/download.
if P0804 = 0, then the file name is clone00.bin
if P0804 = 1, then the file name is clone01.bin
etc.
P0806
BI: Inhibit panel access
0 - 4294967295
0
U, T
-
-
U32
3
Binector input to lock control panel access through external client.
r0807.0
BO: Displays client ac-
cess
- - - - - U16 3
Binector output to display whether command and setpoint source is connected to an external client.
Bit
Signal name
1 signal
0 signal
00
Master control active
Yes
No
P0809[0...2]
Copy command data set
(CDS)
0 - 2 [0] 0 [1] 1
[2] 0
T - - U16 2
Calls 'Copy command data set (CDS)' function. The list of all command data sets (CDS) parameters is
shown in "Index" at the end of the manual.
Example:
Copying of all values from CDS0 to CDS2 can be accomplished by the following procedure:
P0809[0] = 0 Copy from CDS0
P0809[1] = 2 Copy to CDS2
P0809[2] = 1 Start copy
Index:
[0]
Copy from CDS
[1]
Copy to CDS
[2]
Start copy
Note:
Start value in index 2 is automatically reset to '0' after execution of function.

Table of Contents

Other manuals for Siemens SINAMICS V20

Related product manuals