Parameter list
8.2 Parameter list
SINAMICS V20 Converter
Operating Instructions, 10/2019, A5E34559884-012
249
r1024
CO: Actual fixed fre-
quency [Hz]
- - - - - Float 3
Displays sum total of selected fixed frequencies.
r1025.0
BO: Fixed frequency
status
- - - - - U16 3
Displays the status of fixed frequencies.
No On-state for MOP necessary
Defines the operation mode of the motorized potentiometer. See P1040.
P1032
Inhibit reverse direction
of MOP
0 - 1 1 T - - U16 2
Inhibits reverse setpoint selection of the MOP.
Reverse direction is allowed
Reverse direction inhibited
It is possible to change motor direction using the motor potentiometer setpoint (increase/decrease fre-
quency).
Setting 0 enables a change of motor direction using the motor potentiometer setpoint (increase/decrease
frequency).
If P1032 = 1 and P1000 = 1 or 1X, then reverse motor direction will be inhibited.
P1035[0...2]
BI: Enable MOP (UP-
command)
0 - 4294967295 19.13 T - CDS U32 3
Defines source for motor potentiometer setpoint increase frequency.
Digital input 1 (requires P0701 to be set to 99, BICO)
Digital input 2 (requires P0702 to be set to 99, BICO)
Digital input 3 (requires P0703 to be set to 99, BICO)
If this command is enabled by short pulses of less than 1 second, the frequency is changed in steps of 0.1
Hz. When the signal is enabled longer than 1 second the ramp generator accelerates with the rate of
P1036[0...2]
BI: Enable MOP
(DOWN-command)
0 - 4294967295 19.14 T - CDS U32 3
Defines source for motor potentiometer setpoint decrease frequency.
If this command is enabled by short pulses of less than 1 second, the frequency is changed in steps of 0.1
Hz. When the signal is enabled longer than 1 second the ramp generator decelerates with the rate of