EasyManua.ls Logo

Siemens SINAMICS V20

Siemens SINAMICS V20
426 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Parameter list
8.2 Parameter list
SINAMICS V20 Converter
256 Operating Instructions, 10/2019, A5E34559884-012
Parameter
Function
Range
Factory
default
Can be
changed
Scaling
Data
set
Data
type
Acc.
Level
P1124[0...2]
BI: Enable JOG ramp
times
0 - 4294967295 0 T - CDS U32 3
Defines source for switching between jog ramp times (P1060, P1061) and normal ramp times (P1120,
P1121) as applied to the RFG. This parameter is valid for normal mode (ON/OFF) only.
Dependency:
See also P1175.
Notice:
P1124 does not have any impact when JOG mode is selected. In this case, jog ramp times (P1060,
P1061) will be used all the time. If the Dual Ramp function is selected using P1175, ramp times will switch
between normal (P1120, P1121) and JOG (P1060, P1061) ramp times, depending on the settings of
P2150, P2157 and P2159. Therefore, it is not recommended that JOG ramp is selected at the same time
as Dual Ramp.
See P1120.
P1130[0...2]
Ramp-up initial rounding
time [s]
0.00 - 40.00 0.00 U, T - DDS Float 2
Defines rounding time in seconds at start of ramp-up.
Notice:
Rounding times are recommended, since they prevent an abrupt response, thus avoiding detrimental
effects on the mechanics.
Rounding times are not recommended when analog inputs are used, since they would result in over-
shoot/undershoot in the converter response.
Note:
If short or zero ramp times (P1120, P1121 < P1130, P1131, P1132, P1133) are set, the total ramp up time
(t_up) or ramp down time (t_down) will not depend on P1130.
P1131[0...2]
Ramp-up final rounding
time [s]
0.00 - 40.00 0.00 U, T - DDS Float 2
Defines rounding time at end of ramp-up.
Notice:
See P1130
P1132[0...2]
Ramp-down initial round-
ing time [s]
0.00 - 40.00 0.00 U, T - DDS Float 2
Defines rounding time at start of ramp-down.
Notice:
See P1130
P1133[0...2]
Ramp-down final round-
ing time [s]
0.00 - 40.00 0.00 U, T - DDS Float 2
Defines rounding time at end of ramp-down.
Notice:
See P1130
P1134[0...2]
Rounding type
0 - 1
0
U, T
-
DDS
U16
2
Defines the smoothing which is active by setpoint modifications during acceleration or deceleration (e.g.
new setpoint, OFF1, OFF3, REV). This smoothing is applied, if the motor is ramped-up or ramped-down
and
P1134 = 0,
P1132 > 0, P1133 > 0 and
the setpoint is not yet reached.
0
Continuous smoothing
1
Discontinuous smoothing
Dependency:
Effect only when P1130 (Ramp-up initial rounding time) or P1131 (Ramp-up final rounding time) or P1132
(Ramp-down initial rounding time) or P1133 (Ramp-down final rounding time) > 0 s.

Table of Contents

Other manuals for Siemens SINAMICS V20

Related product manuals