Parameter list
8.2 Parameter list
SINAMICS V20 Converter
258 Operating Instructions, 10/2019, A5E34559884-012
Parameter
Function
Range
Factory
default
Can be
changed
Scaling
Data
set
Data
type
Acc.
Level
P1175[0...2]
BI: Dual ramp enable
0 - 4294967295
0
T
-
CDS
U32
3
Defines command source of dual ramp enable command. If binary input is equal to one, then the dual
ramp will be applied. This works as follows:
Ramp-up:
Converter starts ramp-up using ramp time from P1120
When f_act > P2157, switch to ramp time from P1060
Ramp-down:
Converter starts ramp-down using ramp time from P1061
When f_act < P2159, switch to ramp time from P1121
Dependency:
See P2150, P2157, P2159, r2198.
Note:
The dual ramp algorithm uses r2198 bits 1 and 2 to determine (f_act > P2157) and (f_act < P2159). P2150
is used to apply hysteresis to these settings, so the user may wish to change the value of this parameter
to make the dual ramp function more responsive. It is not recommended that the dual ramp function is
used in conjunction with JOG ramp.
See P1124.
r1199.7...12
CO/BO: RFG status
word
- - - - - U16 3
Displays status of ramp function generator (RFG).
Bit
Signal name
1 signal
0 signal
07
Ramp #0 active
Yes
No
08
Ramp #1 active
Yes
No
09
Ramping finished
Yes
No
10
Direction right/left
Yes
No
11
f_act > P2157(f_2)
Yes
No
12
f_act < P2159(f_3)
Yes
No
Note:
See P2157 and P2159.