Parameter list
8.2 Parameter list
SINAMICS V20 Converter
260 Operating Instructions, 10/2019, A5E34559884-012
Parameter
Function
Range
Factory
default
Can be
changed
Scaling
Data set
Data
type
Acc.
Level
P1210
Automatic restart
0 - 8
1
U, T
-
-
U16
2
Configures automatic restart function.
0
Disabled
1
Trip reset after power on, P1211 disabled
2
Restart after mains blackout, P1211 disabled
3
Restart after mains brownout or fault, P1211 enabled
4
Restart after mains brownout, P1211 enabled
5
Restart after mains blackout and fault, P1211 disabled
6
Restart after mains brown- /blackout or fault, P1211 enabled
7
Restart after mains brown- /blackout or fault, trip when P1211 expires
8 Restart after mains brown- /blackout with F3 and leave an interval in seconds de-
termined by P1214, P1211 disabled
9 Restart after mains brown- /blackout with F3 during the attempt time determined by
P1214, P1211 disabled
10 Restart after mains brown- /blackout with F3 during the attempt time determined by
P1214 or manual fault acknowledgment, P1211 disabled
Dependen-
cy:
Automatic restart requires constant ON command via a digital input wire link.
Caution:
P1210 > 2 can cause the motor to restart automatically without toggling the ON command!
Notice:
A "mains brownout" is a very short mains break, where the DC link has not fully collapsed before the power
is reapplied.
A "mains blackout" is a long mains break, where the DC link has fully collapsed before the power is re-
applied.
"Delay Time" is the time between attempts of quitting fault. The "Delay Time" of first attempt is 1 second,
then it will be doubled every next attempt.
The "Number of Restart Attempts" can be set in P1211. This is the number of restarts the converter will try
to quit fault.
When faults are quit and after 4 seconds of no fault condition, "Number of Restart Attempts" will be reset to
P1211 and "Delay Time" will be reset to 1 second.
P1210 = 0:
Automatic restart is disabled.
P1210 = 1:
The converter will acknowledge (reset) faults i.e. it will reset a fault when the power is re-applied. This
means the converter must be fully powered down, a brownout is not sufficed. The converter will not run until
the ON command has been toggled.
P1210 = 2:
The converter will acknowledge the fault F3 at power on after blackout and restarts the converter. It is nec-
essary that the ON command is wired via a digital input (digital input).
P1210 = 3:
For these settings it is fundamental that the converter only restarts if it has been in a RUN state at the time
of the faults (F3, etc.). The converter will acknowledge the fault and restarts the converter after a brownout.
It is necessary that the ON command is wired via a digital input (digital input).