Parameter list
8.2 Parameter list
SINAMICS V20 Converter
284 Operating Instructions, 10/2019, A5E34559884-012
MODBUS on RS485:
Restrictions:
• If the above serial interface controls the converter (P0700 or P0719) then the 1st control word must be
transferred in the 1st PZD-word.
• If the setpoint source is selected via P1000 or P0719, then the main setpoint must be transferred in the
2nd PZD-word.
• When P2012 is greater than or equal to 4 the additional control word (2nd control word) must trans-
ferred in the 4th PZD-word, if the above serial interface controls the converter (P0700 or P0719).