Parameter list
8.2 Parameter list
SINAMICS V20 Converter
292 Operating Instructions, 10/2019, A5E34559884-012
Parameter
Function
Range
Factory
default
Can be
changed
Scaling
Data
set
Data
type
Acc.
Level
P2150[0...2]
Hysteresis frequency
f_hys [Hz]
0.00 - 10.00 3.00 U, T - DDS Float 3
Defines hysteresis level applied for comparing frequency and speed to threshold.
Dependency:
See P1175.
Note:
If P1175 is set, P2150 is also used to control the Dual Ramp function.
P2151[0...2]
CI: Speed setpoint for
messages
0 - 4294967295 1170[0] U, T - DDS U32 3
Selects the source of setpoint frequency, actual frequency is compared with this frequency to detect fre-
quency deviation (see monitoring bit r2197.7).
P2155[0...2]
Threshold frequency f_1 [Hz]
0.00 - 550.00
30.00
U, T
-
DDS
Float
3
Sets a threshold for comparing actual speed or frequency to threshold values f_1. This threshold controls
status bits 4 and 5 in status word 2 (r0053).
P2156[0...2]
Delay time of threshold
freq f_1 [ms]
0 - 10000 10 U, T - DDS U16 3
Sets delay time prior to threshold frequency f_1 comparison (P2155).
P2157[0...2]
Threshold frequency f_2 [Hz]
0.00 - 550.00
30.00
U, T
-
DDS
Float
2
Threshold_2 for comparing speed or frequency to thresholds.
Dependency:
See P1175.
Note:
If P1175 is set, P2157 is also used to control the Dual Ramp function.
P2158[0...2]
Delay time of threshold
freq f_2 [ms]
0 - 10000 10 U, T - DDS U16 2
When comparing speed or frequency to threshold f_2 (P2157) this is the time delay before status bits are
cleared.
P2159[0...2]
Threshold frequency f_3 [Hz]
0.00 - 550.00
30.00
U, T
-
DDS
Float
2
Threshold_3 for comparing speed or frequency to thresholds.
Dependency:
See P1175.
Note:
If P1175 is set, P2159 is also used to control the Dual Ramp function.
P2160[0...2]
Delay time of threshold
freq f_3 [ms]
0 - 10000 10 U, T - DDS U16 2
When comparing speed or frequency to threshold f_3 (P2159) this is the time delay before status bits are
set.
P2162[0...2]
Hysteresis freq. for over-
speed [Hz]
0.00 - 25.00 3.00 U, T - DDS Float 3
Hysteresis speed (frequency) for overspeed detection. For V/f control modes the hysteresis acts below the
maximum frequency.
P2164[0...2]
Hysteresis frequency
deviation [Hz]
0.00 - 10.00 3.00 U, T - DDS Float 3
Hysteresis frequency for detecting permitted deviation (from setpoint) or frequency or speed. This fre-
quency controls bit 8 in status word 1 (r0052).
P2166[0...2]
Delay time ramp up com-
pleted [ms]
0 - 10000 10 U, T - DDS U16 3
Delay time for signal that indicates completion of ramp-up.