Parameter list 
  8.2 Parameter list 
SINAMICS V20 Converter 
Operating Instructions, 10/2019, A5E34559884-012 
295 
P2186[0...2]  
Lower torque threshold 1 
[Nm] 
0.0 - 99999.0  0.0  U, T  -  DDS  Float  3 
Lower limit threshold value 1 for comparing actual torque. 
See P2181 for calculated default value. 
P2187[0...2]  
Upper torque threshold 2 
[Nm] 
0.0 - 99999.0 
Value in 
U, T  -  DDS  Float  3 
Upper limit threshold value 2 for comparing actual torque. 
  This parameter is influenced by automatic calculations defined by P0340. 
See P2181 for calculated default value. 
P2188[0...2]  
Lower torque threshold 2 
[Nm] 
0.0 - 99999.0  0.0  U, T  -  DDS  Float  3 
Lower limit threshold value 2 for comparing actual torque. 
See P2181 for calculated default value. 
P2189[0...2]  
Upper torque threshold 3 
[Nm] 
0.0 - 99999.0 
Value in 
r0333
 
U, T  -  DDS  Float  3 
Upper limit threshold value 3 for comparing actual torque. 
  This parameter is influenced by automatic calculations defined by P0340. 
See P2181 for calculated default value. 
P2190[0...2]  
Lower torque threshold 3 
[Nm] 
0.0 - 99999.0  0.0  U, T  -  DDS  Float  3 
Lower limit threshold value 3 for comparing actual torque. 
See P2181 for calculated default value. 
P2192[0...2]  
Load monitoring delay time 
[s] 
0 - 65  10  U, T  -  DDS  U16  3 
  P2192 defines a delay before warning/trip becomes active.  
- It is used to eliminate events caused by transient conditions.  
- It is used for both methods of fault detection. 
Monitoring word 1 which indicates the state of monitor functions. Each bit represents one monitor function. 
Act. current |r0027| >= P2170 
Output load is not present 
|f_act| > P1082 with delay