Parameter list
8.2 Parameter list
SINAMICS V20 Converter
298 Operating Instructions, 10/2019, A5E34559884-012
Fixed frequencies for PID setpoint can be selected in two different modes. P2216 defines the mode.
1 Direct selection
P2220[0...2]
BI: Fixed PID setpoint
select bit 0
0 - 4294967295 722.3 T - CDS U32 3
Defines command source of fixed PID setpoint selection bit 0.
P2221[0...2]
BI: Fixed PID setpoint
select bit 1
0 - 4294967295 722.4 T - CDS U32 3
Defines command source of fixed PID setpoint selection bit 1.
P2222[0...2]
BI: Fixed PID setpoint
select bit 2
0 - 4294967295 722.5 T - CDS U32 3
Defines command source of fixed PID setpoint selection bit 2.
P2223[0...2]
BI: Fixed PID setpoint
select bit 3
0 - 4294967295 722.6 T - CDS U32 3
Defines command source of fixed PID setpoint selection bit 3.
r2224
CO: Actual fixed PID
setpoint [%]
- - - - - Float 2
Displays total output of PID fixed setpoint selection.
r2224 = 100 % corresponds to 4000 hex.
r2225.0
BO: PID fixed frequency
status
- - - - - U16 3
Displays the status of PID fixed frequencies.
PID-MOP mode specification
No On-state for MOP necessary
Defines the operation mode of the motorized potentiometer. See P2240.
P2232
Inhibit reverse direction of
PID-MOP
0 - 1 1 T - - U16 2
Inhibits reverse setpoint selection of the PID-MOP.
Reverse direction is allowed
Reverse direction inhibited
Setting 0 enables a change of motor direction using the motor potentiometer setpoint (increase/decrease
P2235[0...2]
BI: Enable PID-MOP (UP-
cmd)
0 - 4294967295 0 T - CDS U32 3
Defines source of UP command.