Parameter list
8.2 Parameter list
SINAMICS V20 Converter
302 Operating Instructions, 10/2019, A5E34559884-012
P2268
Minimum value for PID
feedback [%]
-200.00 - 200.00 0.00 U, T - - Float 3
Sets lower limit for value of feedback signal.
When PID is enabled (P2200 = 1) and the signal drops below this value, the converter will trip with F221.
P2268 = 100 % corresponds to 4000 hex.
P2269
Gain applied to PID feed-
back
0.00 - 500.00 100.00 U, T - - Float 3
Allows the user to scale the PID feedback as a percentage value. A gain of 100.0 % means that feedback
signal has not changed from its default value.
P2270
PID feedback function
selector
0 - 3 0 U, T - - U16 3
Applies mathematical functions to the PID feedback signal, allowing multiplication of the result by P2269.
Allows the user to select the transducer type for the PID feedback signal.
Inversion of PID feedback signal
It is essential that you select the correct transducer type. If you are unsure whether 0 or 1 is applicable,
you can determine the correct type as follows:
1. Disable the PID function (P2200 = 0).
2. Increase the motor frequency while measuring the feedback signal.
3. If the feedback signal increases with an increase in motor frequency,
the PID transducer type should be 0.
4. If the feedback signal decreases with an increase in motor frequency the PID transducer type should
be set to 1.
CO: PID scaled feedback [%]
Displays PID scaled feedback signal.
r2272 = 100 % corresponds to 4000 hex.
r2273
- - - - - Float 2
Displays PID error (difference) signal between setpoint and feedback signals.
r2273 = 100 % corresponds to 4000 hex.
Sets PID derivative time.
P2274 = 0: The derivative term does not have any effect (it applies a gain of 1).
Allows user to set proportional gain for PID controller. The PID controller is implemented using the stand-
ard model. For best results, enable both P and I terms.
P2280 = 0 (P term of PID = 0): The I term acts on the square of the error signal.
P2285 = 0 (I term of PID = 0): PID controller acts as a P or PD controller respectively.
If the system is prone to sudden step changes in the feedback signal, P term should normally be set to a
small value (0.5) with a faster I term for optimum performance.