Parameter list
8.2 Parameter list
SINAMICS V20 Converter
Operating Instructions, 10/2019, A5E34559884-012
323
Parameter
Function
Range
Factory
default
Can be
changed
Scaling
Data
set
Data
type
Acc.
Level
P2887[0...1]
CI: CMP 2
0 - 4294967295
0
U, T
4000H
-
U32
3
Defines inputs of Comparator 2, output is r2888.
Index:
See P2869
Dependency:
P2802[13] assigns the Comparator to the processing sequence.
r2888.0
BO: CMP 2
-
-
-
-
-
U16
3
Displays result bit of Comparator 2. See r2811 for the bit field description.
Dependency:
See P2887
P2889
CO: Fixed setpoint 1 in
[%]
-200.00 - 200.00 0.00 U, T - - Float 3
Fixed percent setting 1.
P2890
CO: Fixed setpoint 2 in
[%]
-200.00 - 200.00 0.00 U, T - - Float 3
Fixed percent setting 2.
P2940
BI: Release wobble
function
0 - 4294967295 0.0 T - - U32 2
Defines the source to release the wobble function.
P2945
Wobble signal frequen-
cy [Hz]
0.001 - 10.000 1.000 T - - Float 2
Sets the frequency of the wobble signal.