Options and spare parts
B.1 Options
SINAMICS V20 Converter
Operating Instructions, 10/2019, A5E34559884-012
369
Duty cycle selection
Damage to the braking resistor
Incorrect setting for the duty cycle/voltage could damage the attached braking resistor. Use
the control knob to select the rated duty cycle of the braking resistor.
Value labels on the module have the following meanings:
Duty cycle values labeled are for 230 V converters
Duty cycle values labeled are for 400 V converters
Technical specifications
One phase AC 230 V converters
Three phase AC 400 V converters
RMS current at peak power
Maximum continuous power rating
Maximum continuous current rating
Maximum continuous power rating
1.5 kW 2.75 kW
Maximum continuous current rating
4.0 A 3.5 A
Surrounding air temperature - 10 °C to 50 °C: without derating - 10 °C to 40 °C: without derating
40 °C to 50 °C: with derating
Maximum continuous current rating at
50 ℃ surrounding air temperature
8.0 A 1.5 A
Outline dimensions (L x W x D)
Mounting in a control cabinet (4 x M4 screws)
Short-circuit protection, over-temperature protection
Maximum cable length
• Braking module to converter: 1 m
• Braking module to braking resistor: 10 m
UL file number E121068
Note
Mounting dynamic braking modules side
-by-side causes
derating of power and current to the
mo
dules. To avoid this, Siemens recommends that you observe the clearance requirements
for V20 converters when mounting the dynamics braking modules. For more information, see
Section "
Mounting orientation and clearance (Page 23)".