Commissioning via the built-in BOP
5.1 The built-in Basic Operator Panel (BOP)
SINAMICS V20 Converter
54 Operating Instructions, 10/2019, A5E34559884-012
Button functions
Stops the converter
Single press OFF1 stop reaction: the converter brings the motor to a standstill in the
ramp-down time set in parameter P1121.
Exception:
The button is inactive if the converter is configured for control from terminals
or USS/MODBUS on RS485 (P0700=2 or P0700=5) in AUTO mode.
Double press (< 2 s) or
long press ( > 3 s)
OFF2 stop reaction: the converter allows the motor to coast to a standstill
without using any ramp-down times.
Starts the converter
If the converter is started in HAND/JOG/AUTO mode, the converter running icon (
) appears.
Exception:
This button is inactive when the converter is configured for control from terminals or USS/MODBUS on
RS485 (P0700=2 or P0700=5) in AUTO mode.
Multi-function button
Short press ( < 2 s)
Enters the parameter setting menu or moves to the next screen in the
setup menu
Restarts the digit by digit editing on the selected item
Returns to the fault code display
If pressed twice in digit by digit editing, returns to the previous screen
without changing the item being edited
Long press ( > 2 s)
Returns to the status screen
Enters the setup menu
Short press ( < 2 s)
Switches between status values
Enters edit value mode or change to the next digit
Clears faults
Returns to the fault code display
Long press ( > 2 s)
Quick parameter number or value edit
Accesses fault information data
+
Hand/Jog/Auto
Press to switch between different modes:
Note:
Jog mode is only available if the motor is stopped.