Commissioning via the built-in BOP
5.1 The built-in Basic Operator Panel (BOP)
SINAMICS V20 Converter
54 Operating Instructions, 10/2019, A5E34559884-012
Button functions
Single press OFF1 stop reaction: the converter brings the motor to a standstill in the
ramp-down time set in parameter P1121.
The button is inactive if the converter is configured for control from terminals
or USS/MODBUS on RS485 (P0700=2 or P0700=5) in AUTO mode.
Double press (< 2 s) or
OFF2 stop reaction: the converter allows the motor to coast to a standstill
without using any ramp-down times.
If the converter is started in HAND/JOG/AUTO mode, the converter running icon (
) appears.
This button is inactive when the converter is configured for control from terminals or USS/MODBUS on
RS485 (P0700=2 or P0700=5) in AUTO mode.
Short press ( < 2 s)
• Enters the parameter setting menu or moves to the next screen in the
setup menu
• Restarts the digit by digit editing on the selected item
• Returns to the fault code display
• If pressed twice in digit by digit editing, returns to the previous screen
without changing the item being edited
Long press ( > 2 s)
• Returns to the status screen
• Enters the setup menu
Short press ( < 2 s)
• Switches between status values
• Enters edit value mode or change to the next digit
• Clears faults
• Returns to the fault code display
Long press ( > 2 s)
• Quick parameter number or value edit
• Accesses fault information data
+
Press to switch between different modes:
Note:
Jog mode is only available if the motor is stopped.