Commissioning via the built-in BOP
5.5 Quick commissioning
SINAMICS V20 Converter
Operating Instructions, 10/2019, A5E34559884-012
65
Setting parameters
Note
In the table below, "●" in
dicates that the value of this parameter must be entered according
to the rating
plate of the motor.
Parameter
Access level
Function
Text menu
(if P8553 = 1)
P0100 1
50/60 Hz selection
=0: Europe [kW], 50 Hz (factory default)
=1: North America [hp], 60 Hz
=2: North America [kW], 60 Hz
(EU - US)
P0304[0] ● 1
Rated motor voltage [V]
Note that the input of rating plate data must correspond with the wiring
of the motor (star/delta)
(MOT V)
P0305[0] ● 1
Rated motor current [A]
Note that the input of rating plate data must correspond with the wiring
of the motor (star/delta)
(MOT A)
P0307[0] ● 1
Rated motor power [kW/hp]
If P0100 = 0 or 2, motor power unit = [kW]
If P0100 = 1, motor power unit = [hp]
P0100 = 0 or 2:
(MOT P)
P0100 =1:
(MOT HP)
P0308[0] ● 1
Rated motor power factor (cosφ)
Visible only when P0100 = 0 or 2
(M COS)
P0309[0] ● 1
Rated motor efficiency [%]
Visible only when P0100 = 1
Setting 0 causes internal calculation of value.
(M EFF)
P0310[0] ● 1
Rated motor frequency [Hz]
(M FREQ)
P0311[0] ● 1
Rated motor speed [RPM]
(M RPM)
P1900 2
Select motor data identification
= 0: Disabled
= 2: Identification of all parameters in standstill
(MOT ID)