Commissioning via the built-in BOP
5.6 Function commissioning
SINAMICS V20 Converter
Operating Instructions, 10/2019, A5E34559884-012
93
Ramp-down time for PID setpoint [s]
Range: 0.00 to 650.00 (factory default: 1.00)
P2263 PID controller type = 0: D component on feedback signal (factory default)
= 1: D component on error signal
P2264[0...2] CI: PID feedback Possible sources: 755[0] (Analog input 1), 2224 (Actual fixed PID
setpoint), 2250 (Output setpoint of PID-MOP)
PID feedback filter time constant [s]
Range: 0.00 to 60.00 (factory default: 0.00)
Maximum value for PID feedback [%]
Range: -200.00 to 200.00 (factory default: 100.00)
Minimum value for PID feedback [%]
Range: -200.00 to 200.00 (factory default: 0.00)
Gain applied to PID feedback
Range: 0.00 to 500.00 (factory default: 100.00)
P2270 PID feedback function selector = 0: Disabled (factory default)
= 1: Square root (root(x))
= 2: Square (x*x)
P2271 PID transducer type = 0 : Disabled (factory default)
= 1: Inversion of PID feedback signal
P2274 PID derivative time [s] Range: 0.000 to 60.000
Factory default: 0.000 (the derivative time does not have any effect)
Range: 0.000 to 65.000 (factory default: 3.000)
Range: 0.000 to 60.000 (factory default: 0.000)
PID output upper limit [%]
Range: -200.00 to 200.00 (factory default: 100.00)
PID output lower limit [%]
Range: -200.00 to 200.00 (factory default: 0.00)
Ramp-up/-down time of PID limit [s]
Range: 0.00 to 100.00 (factory default: 1.00)
Gain applied to PID output
Range: -100.00 to 100.00 (factory default: 100.00)
P2350 PID autotune enable = 0: PID autotuning disabled (factory default)
= 1: PID autotuning via Ziegler Nichols (ZN) standard
= 2: PID autotuning as 1 plus some overshoot (O/S)
= 3: PID autotuning as 2 little or no overshoot (O/S)
= 4: PID autotuning PI only, quarter damped response
PID tuning timeout length [s]
Range: 60 to 65000 (factory default: 240)
Range: 0.00 to 20.00 (factory default: 5.00)
CO: Actual fixed PID setpoint [%]
BO: PID fixed frequency status
CO: PID-MOP input frequency of the RFG [%]
CO: Output setpoint of PID-MOP [%]
CO: PID setpoint after PID-RFG [%]
PID setpoint filter time constant [s]
CO: Filtered PID setpoint after RFG [%]
CO: PID filtered feedback [%]
CO: PID scaled feedback [%]
CO: Actual PID output [%]