Start-Up
4.7 Commissioning
4-101
SINUMERIK 802S
6FC5 597–2AA00–0BP2 (01.02)
4.7.4 Completing the start–up
After start–up of the control system by the machine manufacturer, the following should be ob-
served prior to delivery to the end customer:
1. Change the default password for access level 2 from ”EVENING” to your own password.
If the machine manufacturer uses the password ”EVENING” for access level 2 during the
start–up work, the password must be changed.
– Press the softkey Change passw.
– Enter the new password and press OK to confirm.
– Note the password in the Manufacturer Documentation.
2. Reset the access level.
To save the data which have been set during the start–up, an internal data saving is requi-
red. To this aim, set access level 7 (end customer); otherwise, access level 2 will also be
saved.
– Press the softkey Delete passw.
– The access level will be reset.
3. Carry out internal data saving.
– Press the Save data softkey.
4.7.5 Starting up the cycles
Sequence of operations
When loading cycles into the control system, adhere to the following sequence of operations:
1. Save tool compensation data and zero offsets either on the FLASH or on the PG (pro-
gramming device).
These data can be selected from the Services menu by pressing the Data outp./da-
ta...softkey.
2. Load all files of the selected technology path from the toolbox diskette into the control sy-
stem via the V24 interface.
3. Carry out POWER ON.
4. Reload the saved data.