Standard mapping 3-1
2-9
SIPROTEC Modbus - Bus mapping 7UM62
C53000-L1840-C009-03
2.2.20 Registers 10088 to 10091: Binary inputs
2.2.21 Registers 10092 to 10093: Inadvertent energisation protection
2.2.22 Register 10094: Trip coil monitor
2.2.23 Registers 10095 to 10096: Inverse undervoltage protection
2.2.24 Registers 10097 to 10099: Startup supervision of motors
Register
Designation of the
SIPROTEC objects
Comments
Internal
object no.
10088 Ext 1 Gen.TRP 1 = External trip 1: General TRIP 4537
10089 Ext 2 Gen.TRP 1 = External trip 2: General TRIP 4557
10090 Ext 3 Gen.TRP 1 = External trip 3: General TRIP 4577
10091 Ext 4 Gen.TRP 1 = External trip 4: General TRIP 4597
Register
Designation of the
SIPROTEC objects
Comments
Internal
object no.
10092 50/27 picked up 1 = 50/27 picked up 5547
10093 50/27 TRIP 1 = 50/27 TRIP 5548
Register
Designation of the
SIPROTEC objects
Comments
Internal
object no.
10094 FAIL: Trip cir. 1 = 74TC Failure Trip Circuit 6865
Register
Designation of the
SIPROTEC objects
Comments
Internal
object no.
10095 Vp< picked up 1 = Inverse Undervoltage Vp< picked up 6525
10096 Vp< TRIP 1 = Inverse Undervoltage Vp< TRIP 6527
Register
Designation of the
SIPROTEC objects
Comments
Internal
object no.
10097 48 Rot. locked 1 = 48 Rotor LOCKED after Lock. Rotor Time 6822
10098 48 picked up 1 = 48 Starting time supervision picked up 6823
10099 48 TRIP 1 = 48 Starting time supervision TRIP 6821