EasyManua.ls Logo

Siemens SIRIUS 3RA

Siemens SIRIUS 3RA
166 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Insert the connectors on the link module into the corresponding main conductor terminals on the
motor starter protector.
At the same time, insert the guide tabs into the slots provided.
The link module will sit 󹪞ush underneath the motor starter protector on the left- and right-hand
sides.
Snap the reversing starter onto the busbar adapter.
Slide the positioning pieces from below onto the busbar adapter until they engage at the bottom
on the contactors. In the case of contactors in size S0 with AC operation and spring-loaded
connection technology, the lug must be broken o󹪜 (a).
S0 contactors with AC operation and spring-loaded connection system need a spacer (d).
Figure 7-47 Mounting on the busbar adapter (reversing starter, spring-loaded connection system,
size S0)
Mounting the reversing starter (size S2)
The 󹪝gure below shows the work steps for mounting the reversing starter in screw-type
connection system (size S2).
Mounting
7.3 Assembly and disassembly with di󹪜erent mounting systems
SIRIUS 3RA Load Feeders
102 Equipment Manual, 02/2022, A5E03656507520A/RS-AC/004

Table of Contents

Related product manuals