Place the motor starter protector on the DIN rail adapter.
Screw the motor starter protector tight on the DIN rail adapter.
Place the link module on the soft starter from above. At the same time, insert the connectors on
the link module into the corresponding main conductor terminals on the soft starter. A swivel
action is required for this.
Screw the main conductor terminals tight on the soft starter.
Place the soft starter with mounted link module on the bottom of the motor starter protector.
Insert the guide tabs into the slots on the motor starter protector. Insert the connectors into the
corresponding main conductor terminals.
Screw the main conductor terminals tight on the motor starter protector.
Screw the soft starter tight on the DIN rail adapter. The feeder sits tight on the adapter.
Tightening torque: 1.5 ... 1.6 Nm
Mounting
7.3 Assembly and disassembly with di󹪜erent mounting systems
SIRIUS 3RA Load Feeders
Equipment Manual, 02/2022, A5E03656507520A/RS-AC/004 75