Technical data
10.4 Outputs
SITRANS F Ultrasonic flowmeters FST030 (HART)
116 Operating Instructions, 08/2017, A5E35971532-AC
Cable Standard industrial signal cable with up to 3 twisted pairs with overall screen can be con-
nected between the transmitter and the control system. Individual pair or overall screen is
optional depending on user requirements.
Voltage range Max. 24 V DC (active)
Table 10- 8 Current output (Channels 2 to 4)
Load
• Ex i: <470 Ω
• Non-Ex: <770 Ω
Time constant (adjustable)
Fault current
Measurement range (mA)
Lower fault current (mA)
4-20 NAMUR
3.8 - 20.5
3.5
4-20 US
4.0 - 20.8
3.75
4-20 NAMUR
4.0 - 20.5
2.0
4-20 US
4.0 - 24.0
2.0
0-20 NAMUR
0.0 - 20.5
0.0
0-20 US
0.0 - 24.0
0.0
Customized fail-safe mode
• Last valid value
– Lower fault current
– Upper fault current
• Fail-safe value
• Current value
Galvanic isolation All inputs and outputs are galvanically isolated PELV circuits with 60 V DC isolation from
each other and ground.
Maximum test voltage: 500 V AC
Cable Standard industrial signal cable with up to 3 twisted pairs with overall screen can be con-
nected between the transmitter and the control system. Individual pair or overall screen is
optional depending on user requirements.
Voltage range Max. 24 V DC (active)
Table 10- 9 Digital output
41.6 µs to 5 s pulse duration
0 to 10 kHz, 50 % duty cycle, 120 % overscale provision
Time constant (adjustable) 0 to 100 s
0 to 24 V DC, 87 mA, short-circuit-protected