Technical data
10.4 Outputs
SITRANS F Ultrasonic flowmeters FST030 (HART)
Operating Instructions, 08/2017, A5E35971532-AC
115
Cable
• Standard industrial signal cable with up to 3 twisted pairs with
overall screen can be connected between the transmitter and the
control system. Individual pair or overall screen is optional depend-
ing on user requirements.
Voltage range Max. 24 V DC (active)
14 to 30 V DC (passive)
Table 10- 6 Channels 5 and 6 input (RTD)
-50 to 250°C (-58 to 482°F)
Resolution <0.1 mK
+/- 0.25 K (calibrated 4 wire)
Table 10- 7 Current output (Channel 1)
Load
• Ex i: <470 Ω (HART ≥ 230 Ω)
• Non-Ex: <770 Ω (HART ≥ 230 Ω)
Time constant (adjustable)
Fault current
Measurement range (mA)
Lower fault current (mA)
4 - 20 NAMUR
3.8 - 20.5
3.5
4 - 20 US
4.0 - 20.8
3.75
Customized fail-safe mode
• Last valid value
• Lower fault current
• Upper fault current
• Fail-safe value
• Current value
Galvanic isolation All inputs and outputs are galvanically isolated PELV circuits with 60 V DC isolation from
each other and ground.
Maximum test voltage: 500 V AC