Diagnosing and troubleshooting
9.3 Device status icons
SITRANS F Ultrasonic flowmeters FST030 (HART)
Operating Instructions, 08/2017, A5E35971532-AC
89
Siemens standard alarm classes
Icon
Priority
level
Name
Description
1 Maintenance failure
Maintenance alarm: maintenance demanded immediately
Measurement values are not valid
5 Maintenance warning
Maintenance warning
Measured signal still valid
6 Maintenance required
Maintenance required
Measured signal still valid
3 Process value alarm
Process value has reached an alarm limit
4 Process value warning
Process value has reached a warning limit
2 Function check
Change of configuration, local operation, or substitute value entered
Output signals are temporarily invalid
NAMUR status signals
Icon
Priority
level
Name
Description
1 Failure
Failure
Invalid output signal
3 Out of specification
Out of specification
Device will still work, but output signals may be invalid
4 Maintenance required
Maintenance request
Measured signal still valid
2 Function check
Function check
Output signal temporarily invalid