Safety notes
2.2 Installation in hazardous location
SITRANS F M MAG 5000/6000
Operating Instructions, 12/2013, A5E02338368-002 13
Appropriate cable connectors are used for the output cicuits: intrinsically safe: blue, non-
intrinsically safe: black
Sensor and transmitter are connected to the potential equalization. For intrinsically safe
output circuits potential equalization must be maintained along the entire connection path.
Sensor insulation thickness is max. 100mm (only insulated sensors).
EN50281-1-2 is considered for installation in areas with combustible dust.
When protective earth (PE) is connected, no potential difference between the protective
earth (PE) and the potential equalization (PA) can exist, even during a fault condition.