SITRANS F M MAG 5000/6000
Operating Instructions, 12/2013, A5E02338368-002 63
11.1 Technical specifications
Mode of operation and design
Electromagnetic with pulsed constant field
Detection of empty pipe (special cable
required in remote mounted installation)
Electrode input impedance
11 ... 30 V DC, R
i
= 4.4 KΩ
I
DC 11 V
= 2.5 mA, I
DC 30 V
= 7 mA
0 ... 20 mA or 4 ... 20 mA, Alarm
0.1 … 30 s, adjustable (for batch: fixed at 0.1
s)
0 ... 10 kHz, 50% duty cycle
(uni/bidirectional)
DC 24 V, 30 mA, 1 kΩ ≤ R
i
≤10 kΩ, short-
circuit protected (power supplied from
flowmeter)
DC 3 … 30 V, max. 110 mA, 200 Ω ≤ R
i
≤10
kΩ (powered from connected equipment)
0.1 … 30 s, adjustable (for batch: fixed at 0.1
s)
Changeover relay, same as current output
0 ... 9.9% of maximum flow
All inputs and outputs are galvanically isolated
Max. measuring error
(incl. sensor and zero point)
0.4% ± 1 mm/s (for v > 0.1 m/s)