SITRANS F M MAG 5000/6000
Operating Instructions, 12/2013, A5E02338368-002 61
Power supply
Check MAG 5000/6000 for bended
pins on the connector
2. MAG 5000/6000 defective
1. Current output disabled
2. Digital output disabled
3. Reverse flow direction
Incorrect or no coil current
Ensure that the measuring pipe is full
1. No load on current output
2. MAG 5000/6000 defective
Switch off MAG 5000/6000, wait 5
sec. and switch on again
Indicates flow with no
flow in pipe
Select empty pipe cut-off
Empty pipe cut-off is OFF
Ensure that the measuring pipe is full
Electrode connection
missing/electrode cable is
insufficiently screened
Ensure that electrode cable is
connected and sufficiently screened
2. Conductivity of medium too
low
Use special electrode cable
3. Electrical noise potential
between medium and sensor
Ensure sufficient potential
equalization
Ensure medium does not contain air
bubbles
5. High concentration of
particles or fibres
Replace SENSORPROM
®
unit or
reset SENSORPROM
®
unit with MAG
CT transmitter
Defective SENSORPROM
®
unit
Wrong type of
SENSORPROM
®
unit