EasyManua.ls Logo

Siemens SITRANS F M MAG 5000 - A.2 Basic settings

Siemens SITRANS F M MAG 5000
106 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Menu diagrams
A.3 Current output
SITRANS F M MAG 5000/6000
Operating Instructions, 12/2013, A5E02338368-002 77
A.3 Current output
1)
If HART communication is installed, it is not possible to set the output for 0-20 mA (even
though the option is visible in the display). This is due to the fact that HART does not work if
the output falls below 2-3 mA.
2)
4-20 mA + Alarm is the default setting for MAG 6000 I. For all other variants, the default setting
is 4-20 mA.
3)
The controlling of alarm levels does not recognize if the jumper is mounted for passive output.
Do not combine differentiation and low alarm level together with passive output. The output will
try to pull down the level to 1.3 mA at fatal errors which is not possible for passive output.

Table of Contents

Other manuals for Siemens SITRANS F M MAG 5000

Related product manuals