EasyManua.ls Logo

Siemens SITRANS F Modbus RTU RS 485 - Modbus Functions Codes; Addressing and Command Overview

Siemens SITRANS F Modbus RTU RS 485
76 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Functions codes
6
6.1 Modbus Commands
Modbus addressing model
The module allows R/W access to the following standard Modbus data register blocks:
Coils (ref. 0x address range)
Holding Registers (ref. 4x address range)
I.e. the module will not support the other standard data register blocks:
"Discrete Input" (ref. 1x address range)
"Input Registers"(ref. 3x address range)
Commands
Broadcast communication from master to slave(s) through device address 0 is supported. No
response from the slave is generated in that case. Broadcast communication is not secured by
the normal check mechanisms and shall be limited to very few uses.
A SITRANS F Modbus slave only recognizes (and accepts) few Modbus RTU commands/function
codes.
Supported function codes are listed in the table below.
Table 6-1 Function codes
Function code Command text Description
01 hex Read coils Reads the status of single bit(s) in a slave
03 hex Read multiple registers Reads the binary content of multiple 16-bit registers in the slave. The
maximum number of registers is 26
05 hex Write single coil Writes a single on/o󹪜 bit
10 hex Write multiple registers Preset values into a sequence of 16-bit registers. The maximum num‐
ber of registers is 25
11 hex Report Slave ID The SITRANS F slave will respond to a Report Slave ID command
(Command 17) request from the master by giving in formation about
device type, vendor, revision level etc. in a format as shown
Modbus RTU RS 485
Operating Instructions, 03/2021, A5E00753974-AB 23

Related product manuals