A.12 Flowmeter status
Table A-24 Flowmeter status
MODBUS regis‐
ter
MODBUS ad‐
dress
No. of bytes Data type Description Read / write
4:03201 3200 2 Word System status:
• bit0=RunIndicator
• bit1=ErrorPendingOn
• bit2=ErrPendChanged
• bit3=Batching
• bit4=BatchPaused
• bit5=Zeroadjusting
• bit6=Totalizer1Hold
• bit7=Totalizer2Hold
R
4:03202 3201 2 Word Error pending 1* (oldest/rst error)
• 0xFFFF = no error
R
4:03203 3202 2 Word Error pending 2* R
4:03204 3203 2 Word Error pending 3* R
4:03205 3204 2 Word Error pending 4* R
4:03206 3205 2 Word Error pending 5* R
4:03207 3206 2 Word Error pending 6* R
4:03208 3207 2 Word Error pending 7* R
4:03209 3208 2 Word Error pending 8* R
4:03210 3209 2 Word Error pending 9* R
4:03211 3210 2 Byte Batch status
• 0 = Idle
• 1 = Ready
• 2 = Running
• 3 = Paused
R
Table A-25 Zero adjust progress, MAG 6000
MODBUS regis‐
ter
MODBUS ad‐
dress
No. of bytes Data type Description Read / write
4:03212 3211 2 Byte Zero adjust progress
• 0 = Idle
• 1 = Ready
• 2 = Running
R
Modbus holding registers
A.12 Flowmeter status
Modbus RTU RS 485
Operating Instructions, 03/2021, A5E00753974-AB 57