A.7 External input
Table A-14 External input, MAG 6000
MODBUS regis‐
ter
MODBUS ad‐
dress
No. of bytes Data type Description Read / write
4:02301 2300 2 Byte Input Function:
• 0 = O
• 1 = Start Batch
• 2 = Hold/Continue
• 3 = Stop Batch
• 4 = Zero Adjust (only SV)
• 5 = Totalizer reset
• 6 = Force output
• 7 = Freeze output
• 8 = Qmax 2 (night)
• 9 = Manual cleaning
R/W
4:02302 2301 2 Byte Totalizer reset:
• 0 = Totalizer 1
• 1 = Totalizer 2
• 2 = Totalizer 1 + 2
R/W
4: 02303 2302 4 Float Force output (1/100%) R/W
Table A-15 External input, MASS 6000
MODBUS regis‐
ter
MODBUS ad‐
dress
No. of bytes Data type Description Read / write
4:02301 2300 2 Byte Input Function:
• 0 = O
• 1 = Start Batch
• 2 = Hold/Continue
• 3 = Stop Batch
• 4 = Zero Adjust
• 5 = Totalizer reset
• 6 = Force output
• 7 = Freeze output
R/W
4:02302 2301 2 Byte Totalizer reset:
• 0 = Totalizer 1
• 1 = Totalizer 2
• 2 = Totalizer 1 + 2
R/W
4: 02303 2302 4 Float Force output (1/100%) R/W
Modbus holding registers
A.7 External input
Modbus RTU RS 485
50 Operating Instructions, 03/2021, A5E00753974-AB