Appendix A
A.1 I/O Connections and Wiring
SITRANS FUH1010 Quick Start
42 Operating Instructions (Compact), 12/2008, CQO:QSG010 Revision A
Terminal Block Wiring - 1010DXS2-7
(Refer to manual drawing 1010DXS2-7 sheet 3 of 4. When Barriers are used, isolation is
limited to the Barrier's working voltage. Refer to table on manual drawing 1010-341 sheet 3).
These connection diagrams apply to the part numbers listed below.
Table A- 4 Part Numbers and Connection Diagrams
1010DXS2-7 (Sheet 3 of 4) Drawing
FUH1010 7ME3601-ab
where:
a= 3
b= D or F
Note
See Table A-2 Wiring diagram.
Table A- 5 FUH1010 Input/Output Wiring (TB1)
Pin# Signal Function Description
1 Io2 - Isolated Loop Return
2 Io2 + Isolated Loop Supply
3 Io1 - Isolated Loop Return
4 Io1 + Isolated Loop Supply
4-20mA output
proportional to any
available spanned data
variable
4-20mA assignable and
spannable under menu
control.
5 ANIN 2 4-20mA Input Ch.2
6 ANIN 1 4-20mA Input Ch.1
4-20mA Analog input
non-isolated
User assignable depending
on model - may be AUX, PSI,
etc.)
7 Status -1 Status Bit Return Ch.2 Status Alarm
Emitter
8 Status +1 Status Output Ch.1 Status Alarm
Collector
9 Status -2 Status Bit Return Ch.2 Status Alarm
Emitter
10 Status +2 Status Output Ch.2 Status Alarm
Collector
User assignable via menu
control.
Note
Wiring diagram is the same as Table A-3.