SFIDK.PS.029.E5.02 / SW 2.01.0718
4.2 Operation (HART communication)
The device can be operated with:
operating and display panel
HART-Communicator
PC/Laptop and software SIMATIC PDM with HART modem (coupling module)
Electrical connection of PC/Laptop with HART modem and HART-Communicators to 4 - 20 mA
signal line is shown in figure below.
Electrical connection, schematic diagram
Warning
Do not use coupling module (HART modem) in hazardous areas and do not connect to
intrinsically safe circuits.
Digital output DA2
(relay output) type of protection Intrinsic Safety Ex ia IIC/IIB
Terminals 3 and 4
only for connection to a certified intrinsically
safe circuit.
Max. values:
Ui = 30 V
Ii = 100 mA DC
Ii = 50 mA AC
Ci = 24 nF
Li = 73 uH
(≤ 330 Ohm for
Ex-version)