Installation
4.1 Mounting
SITRANS LVS100/200
16 Operating Instructions, 01/2019, A5E44839609-AA
SITRANS LVS100/200 is normally mounted into the vessel top for full detection, or through
the tank wall at the detection level, for full, demand, or empty detection.
Position tines vertically to avoid product
buildup: use a 50 mm open
-end wrench to
turn the process connection until the tine
orientation marking faces up or down.
Use angle mounting for flowing material
only. If angle mounting is required with high
material loading, customer
-supplied protec-
tion from falling material must be in place.
Cable extension version
Rigid extension with sliding sleeve
Protection in case of high material loading.
Cable gland faces downward to avoid water penetration.
Tine orientation marking facing sideways.
Angle mounting
max. deviation from vertical α
max. length L
4 m
45°
1.2 m
>45°
0.6 m