ST750 GENERAL HANDBOOK
667/HB/33750/000 Page 114 Issue 6
ST750 LED 2 Phase Drive PCB
ST750 LED 4 Phase Drive PCB
A.2.2 – FUSES
See Appendix A.3 for details of where these fuses are used
16A HRC cartridge fuse (Pre Nov 2003)
20A MCB SP C Type (Post Nov 2003)
Solar and Neutral Softwire kit
Phase Softwire kit 2/4 phases (incl audio drives)
Phase Softwire kit 5/6 phases (incl audio drives)
Manual Panel – signs on off only
A.3- FUSE RATINGS AND POSITIONS
Electricity Company Cut-out Fuse
The maximum size of this fuse should not
exceed 45A (without reference to Poole).
Maximum prospective short circuit current must
not exceed 16,000A. Rating depends on
application but 25A min is recommended up to
18A load
Master Switch Panel - MCB
516/4/97076/010
20A MCB SP C Type on the Master Switch Panel
Maintenance Socket Fuse
518/4/90638/000
5A HRC cartridge fuse to BS1361 marked
‘MAIN,T’ on Master Switch Panel.