User Manual For - CONTROLLER/DATA RECORDER MultiCon CMC-99/141
Low Limit
parameter set as
0mA
,
High Limit
parameter set as
20mA
,
Scaling
parameter set as
linear
,
press the
Configure scaling
button,
in
Output unit
parameter write
A
,
in
Input value
parameter in the
Point 1
section write
0mA
,
in
Output value
parameter in the
Point 1
section write
0A
,
in
Input value
parameter in the
Point 2
section write
20mA
,
in
Output value
parameter in the
Point 2
section write
5A
,
for
Display
block parameters,
Format
parameter set as
numeric
,
Precision
parameter set as
0.0
,
in
Graph low
parameter write
0A
,
in
Graph high
parameter write
5A
,
all the other parameters should be on default settings,
The configuration steps are shown in
Fig. 7.64
.
b) For voltage,
using the arrows in the top navigation bar, select any
logical channel
such as 21,
in the
Name
parameter write
Voltage"
,
Mode
parameter set as
Hardware input
,
Source
parameter set as
Inp. A5: Voltage
(see the connection in
Fig. 7.63
),
press the
Source configuration
button to set the source configuration options:
Mode
parameter set as
0-10V
, because this voltage range comes from
the voltage converter,
Low Limit
parameter set as
0V
,
High Limit
parameter set as
10V
,
Scale
parameter set as
linear
,
press the
Configure scaling
button,
in
Output unit
parameter write
V
,
in
Input value
parameter in the
Point 1
section write
0V
,
in
Output value
parameter in the
Point 1
section write
0V
,
in
Input value
parameter in the
Point 2
section write
10V
,
in
Output value
parameter in the
Point 2
section write
400V
,
for
Displaying
block parameters,
Format parameter set as
numeric
,
Precision
parameter set as
0.0
,
in
Graph low
parameter write
0V
,
in
Graph high
parameter write
400V
,
all the other parameters should be on default settings,
122

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Simex MultiCon CMC-99/141 and is the answer not in the manual?

Simex MultiCon CMC-99/141 Specifications

General IconGeneral
BrandSimex
ModelMultiCon CMC-99/141
CategoryController
LanguageEnglish

Related product manuals