Most important parameters of IO2, IO4, IO6 and IO8 modules:
IO2 IO4 IO6 IO8
Number of
outputs
2 4 6 8
Output type Passive current
output
Passive current
output
Passive current
output
Passive current
output
Nominal
analogue range
4-20mA 4-20mA 4-20mA 4-20mA
Hardware
output limitation
3-25mA 3-25mA 3-25mA 3-25mA
Output state
when the
device is off
27.4mA 27.4mA 27.4mA 27.4mA
Output voltage
dropout
max. 9V max. 9V max. 9V max. 9V
Overload
protection
Internal resettable
fuse 50mA
Internal resettable
fuse 50mA
Internal resettable
fuse 50mA
Internal resettable
fuse 50mA
Loop Supply
Range
9-30V 9-30V 9-30V 9-30V
Output current
precision
0.1% @25ºC,
50ppm/ºC
0.1% @25ºC,
50ppm/ºC
0.1% @25ºC,
50ppm/ºC
0.1% @25ºC,
50ppm/ºC
Resolution 12 bit 12 bit 12 bit 12 bit
Isolation
strength
1 min @ 500V AC 1 min @ 500V AC 1 min @ 500V AC 1 min @ 500V AC
Weight 23g 30g 38g 53g
Tab. 8.23 Technical data for the module IO2, IO4, IO6 and IO8
305

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Simex MultiCon CMC-99/141 and is the answer not in the manual?

Simex MultiCon CMC-99/141 Specifications

General IconGeneral
BrandSimex
ModelMultiCon CMC-99/141
CategoryController
LanguageEnglish

Related product manuals