User Manual For - CONTROLLER/DATA RECORDER MultiCon CMC-99/141
Logical channel 2: Overhead alarm threshold:
In
Name
parameter write:
Overhead alarm threshold
,
Mode
parameter set as:
Set point value
,
Edit button
parameter set as:
enabled
,
In
Unit
parameter write:
mA
,
Precision
parameter set as:
0.00
,
In
Graph low
parameter write:
0
,
In
Graph high
parameter write:
22
,
All other parameters should be set as default,
Logical channel 3: Bottom alarm threshold:
In
Name
parameter write:
Bottom alarm threshold
,
Mode
parameter set as:
Set point value
,
Edit button
parameter set as:
enabled
,
In
Unit
parameter write:
mA
,
Precision
parameter set as:
0.00
,
In
Graph low
parameter write:
0
,
In
Graph high
parameter write:
22
,
All other parameters should be set as default,
Logical channel 4: Alarm displaying:
In
Name
parameter write:
Alarm state
,
Mode
parameter set as:
Hardware output monitor
,
Source
parameter set as:
Out.V1 : Virtual relay
,
Format
parameter set as:
binary
,
In
Off-state text
parameter write:
No alarm
,
In
On-state text
parameter write:
ALARM!
,
In
Graph low
parameter write:
0
,
In
Graph high
parameter write:
22
,
Now we go to
Channel highlight
submenu:
Highlight color
parameter set as:
1
,
Mode
parameter set as:
blinking
,
In
Blink period
parameter write:
1
,
In
Trig.hold time
parameter write:
1
,
Trigger
parameter set as logical channel that we are currently configuring
(in this task, it will be Logical channel 4 named
Alarm state
),
Alarm state
parameter set as:
no highlight
,
Now, go to
Color
parameter and set font color (at the top of the screen) and
background color (at the bottom of the screen),
For
Highlight color
2
and
3
, set
Mode
parameter as
disabled
,
Virtual relay V1: Defining the proper time to activate the alarm:
Mode
parameter set as:
outside range
,
Source
parameter set as logical channel named
Current value
,
Alarm state
parameter set as:
immed. ON
,
Level mode
parameter set as:
channel
,
Lower level
parameter set as logical channel named
Overhead alarm
threshold
,
Upper level
parameter set as logical channel named
Bottom alarm threshold
,
All other parameters should be set as default,
90

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Simex MultiCon CMC-99/141 and is the answer not in the manual?

Simex MultiCon CMC-99/141 Specifications

General IconGeneral
BrandSimex
ModelMultiCon CMC-99/141
CategoryController
LanguageEnglish

Related product manuals