EasyManua.ls Logo

Simplex 4001-9403 - Page 17

Simplex 4001-9403
40 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6. If waterflow/sprinkler switch circuits are used, connect as follows:
A. Connect the waterflow switch (normally open) as shown in Figure 15. Make sure 3.3K resistor is connect to
circuit as shown in wiring diagram 841-610.
B. Connect the sprinkler tamper switch (normally closed) as shown in Figure 15. Make sure resistors (1 K and
820 ohm, 1 watt) are connected to circuit as shown in wiring diagram 841-610.
Note: If the system contains the transient suppressor, zone disconnect or transient suppressor/zone disconnect
board, connect the waterflow/sprinkler circuits to the board instead of the panel terminals (see Page 18).
TO WATERFLOW SW AND SPRINKLER
TAMPER SW (IF SUPPRESSOR/DISCONNECT
ED IS NO_T USED)
FIGURE 15
7. If using a remote annunciator or remote annunciator with remote trouble station and remote acknowledge
switch, connect to panel as follows (see Fig. 16, page 14, for reference):
Notes: 1. Perform only Steps 7A through 7C if you are installing the 4601-9101 remote annunciator.
2. Perform Steps 7A through 7E if you are installing the 4601-9102 remote annunciator with trouble and
acknowledge.
A. Connect the annunciator - wires as indicated in Table 2.
B. If supervision of annunciators is desired, remove the appropriate jumper(s) and resistor(s) indicated in Table
2.
C. Connect the RMT + wire to TB3-9 (RMT +).
D. Connect the REM ACK wire to TB2-1 (REM ACK).
E. Connect the TBL RMT wire to TB3-8 (TBL RMT).
TABLE 2
I
ZONE
I
TERMINAL
I
JUMPER REMOVED
RESISTOR REMOVED
(See Caution Below)
(See Caution Below)
I
1
TB3-4 (ANNl-)
JW4
R84
2 (if used) TB3-5 (ANN2-)
JW5
R85
3 (if used) TB3-6 (ANNS-)
JW6
R86
4 (if used) TB3-7 (ANN4-)
JW7
R87
CAUTION: If alarm relay module is used, DO NOT REMOVE JUMPERS OR RESISTORS!
13
firealarmresources.com

Related product manuals