EasyManua.ls Logo

Simplex 4001-9403 - Page 18

Simplex 4001-9403
40 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
CONTROL PANEL TERMINAL CONNECTIONS - Continued
162
JW4 JW5 JW6 JW7
FIGURE 16
8. If 4100-9810 alarm relay module is used, connect it to TB2, TB3, and TB5 on the panel as follows (refer to
Figure 16):
A. Connect the relay module’s ANN1 wire (TBl-1) to TB3-4 (ANNl-).
Connect the relay module’s ANN2 wire (TBl-2) to TB3-5 (ANN2-).
Connect the relay module’s ANN3 wire (TBl-3) to TB3-6 (ANN3-).
Connect the relay module’s ANN4 wire (TBl-4) to TB3-7 (ANN4-).
B. Connect the relay module’s AUX- wire (TB2-8) to TB2-4 (AUX-).
Connect the relay module’s AUX+ wire (TB2-7) to TB5-6 (NO of AUXl).
C. Connect a wire from the panel’s RMT+ (TB3-9) to TB5-7 (C of AUXl).
D. Refer to wiring diagrams 841-610 for information on connecting external devices.
9. If remote trouble devices are used, connect them to trouble relay as follows (Refer to Fig. 17):
The trouble relay may be used to operate external circuits. These external circuits may contain horns, bells,
lights, or other devices associated with fire alarm systems.
Notes: 1. Trouble relay activates upon a trouble condition.
l
Trouble silence switch activation turns off the trouble relay.
2. Trouble relay contacts are Form C dry contacts, and are rated 2A maximum at 30VACMOVDC
(resistive rating).
A. Connect positive (DC) or hot (AC) lead of voltage source to TB3-2 (the common [C] contact of the trouble
relay).
B. If devices are to be turned on during a trouble condition, connect lead from remote devices to TB3-3 (the
normally open [N/O] contact of the trouble relay); if devices are to be turned off during a trouble condition,
connect lead from remote devices to TB3-1 (the normally closed [N/C] contact of the trouble relay.
14
firealarmresources.com

Related product manuals