32
10. Install battery charger options as required.
For external batteries and charger, install jumper to position 1-2 on P4
of 565-367 or 565-593 Power Supply.
To charge 18 Ah or 10 Ah lead-acid batteries, install jumper to
position 2-3 on P4 of 565-367 or 565-593 Power Supply.
11. Install battery switch over option as required.
For automatic switch to battery upon power failure, install jumper to
position 2-3 on P3 of 565-367 or 565-593 Power Supply.
For switch to battery on signal from Voice Controller, install jumper to
position 1-2 on P3 of 565-367 or 565-593 Power Supply.
12. If 4003 is being used in either Adjunct Mode or 4020 Slave Mode, install
0V connection to host FACP.
Connect a 12 AWG copper wire from TB2-3 to 0V on the battery block
of the host FACP.
13. Connect AC power leads to TB3 on the 565-367 Power Supply. If 565-593
Power Supply is used, connect AC power to the flying leads of the
transformer.
14. Apply system power.
15. If using internal batteries, connect as indicated.
16. If using external batteries from FACP, connect as indicated.
17. Test the system.
Panel Terminal Connections, Jumper Placements, and DIP Switch
Settings,
Continued
Procedure, (continued)