Back Box Mounting
The back box can be surface-mounted or semi-flush mounted to the
wall. Use separate conduit entrances for power-limited and non-power
limited wiring.
AC supply, battery supply, and City Connect wiring are all non-power
limited wiring.
Removing Electronics Assembly
Use either a #6 Torx or a slot-head screwdriver to remove the four
screws that secure the electronics assembly to the back box.
Conduit Entrances and Wire Routing
Nine knockouts are provided for conduit connection. Refer to Fig-
ure 2-1 for knockout locations.
Power limited wiring must be located only in the shaded area of
the cabinet.
AC power (non-power limited) wiring must be run in separate con-
duit from all other wiring, as shown in Figure 2-1. Non-power lim-
ited wiring must be separated from power limited wiring by a
minimum of 1/4".
Figure 2-1 Power-Limited (Shaded) and
Non-Power Limited Wiring Areas
Expansion
Power Supply
TB1 TB2 TB3
Battery
AC Voltage
Connection
Battery
Connection
Battery
DACT
City Connect
Module
In This Chapter
Back Box Mounting . . . . . . . . . . . . . . . . . . . . .2-1
General Wiring Guidelines . . . . . . . . . . . . . . . .2-2
IDNet Wiring. . . . . . . . . . . . . . . . . . . . . . . . . . .2-3
Class A/Class B NAC Wiring . . . . . . . . . . . . . .2-5
Remote Annunciator Comm Wiring . . . . . . . . .2-8
Digital Alarm Communicating Transmitter (DACT)
Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-9
Auxiliary 24V Power Wiring . . . . . . . . . . . . . . 2-11
City Connect Module Wiring. . . . . . . . . . . . . .2-12
Auxiliary Relay Wiring . . . . . . . . . . . . . . . . . .2-13
AC Supply Wiring . . . . . . . . . . . . . . . . . . . . . .2-14
Battery Wiring. . . . . . . . . . . . . . . . . . . . . . . . .2-15
Depleted Battery Cutout. . . . . . . . . . . . . . . . .2-16
Safety Ground/Ferrite Bead . . . . . . . . . . . . . .2-16
Replacing Lithium Battery . . . . . . . . . . . . . . .2-17
Periodic Testing and Maintenance . . . . . . . . .2-17
Chapter 2. Installation/System Checkout
Technical Manuals Online! - http://www.tech-man.com