Chapter 8. Operating
8-7
1. Press the <MENU> key. Press <NEXT> or <PREV>
until the [Walktest] option is displayed. Press
<ENTER>. The following displays:
<ENTER>=Accept
[Off] Lg Sil NoPr
2. For each option, use the <NEXT> and <PREV> keys to
scroll through the option’s choices. Use the right and
left arrow keys to move from one option to another.
Available options include
ON/OFF. Used to enable and disable WalkTest.
When set to ON, a WalkTest Enabled trouble is dis-
played on the panel.
LG/NL. Controls whether alarms and troubles gen-
erated by WalkTest are sent to the alarm or trouble
log. Lg enables logging; NL disables logging.
SIG/SIL. Controls whether the NACs are used to
signal activation of an alarm or trouble condition.
SIG enables NACs for Walktest; SIL disables
NACs for WalkTest.
PR/NoPR. Enables (PR) or disables (NoPR)
whether WalkTest alarms and troubles are sent to
the locally attached printer.
3. When the options are set, press the <ENTER> key. The
system prompts you to confirm the settings. Press
<ENTER> again to confirm.
Advanced Operations
Upload/Download
Uploading and downloading files allows you to transfer the
panel’s job file between a service PC and the panel. The term
Uploading refers to transferring a job file from the panel to a
PC; whereas, the term Downloading refers to moving a job
file from the PC to the panel.
Note: The UPLD/DWNLD menu option enables the panel
for an upload or download operation. This option does not,
however, perform the transfer operation. A service PC, run-
ning the panel’s PC programmer tool, is required.
1. Press <MENU>.
2. Use the <NEXT> or <PREV> keys to scroll to the
UPLD/DWNLD menu choice.
3. Press <ENTER>. A prompt similar to the following
appears.
<ENTER>=Accept
XFER: [Start XFER]
Restarting the CPU
This option is used to clear an Access Level 4 Trouble (i.e., a
“Service Mode Trouble”).
1. Press <MENU>.
2. Press <NEXT> and <PREV> and choose one of the fol-
lowing options.
Warm. Clears the Access Level 4 trouble, restarts
the panel, but preserves the panel’s non-volatile
memory, including time/date information, historical
logs, and all currently disabled points
Cold. Clears the Access Level 4 trouble and re-ini-
tializes the panel’s non-volatile memory, clearing
all time/date information, historical logs, and dis-
abled points.
3. Choose an option and press <ENTER>. System startup
prompts appear on the screen, followed by the system
status message.
Viewing Software Revision Number and Job Info
1. Press <MENU>.
2. Press <NEXT> or <PREV> until Software Rev is
shown. Press <ENTER>. A message similar to the fol-
lowing appears, displaying the revision level of the
panel’s software.
Rev 1.00.11
<NEXT> = View Job Info
3. Press <NEXT> to see the job revision number (i.e., the
number of times the job has been edited and saved), and
the date on which the panel was edited.
JOB REV:1
12:00:00 am 04/09/04