Chapter 8. Operating
8-6
<ENTER>=Accept
Menu: [Diagnostics]
3. Press <ENTER>. A prompt similar to the following 
appears.
<ENTER>=Accept
Diag: [BAT CHGR METR]
4. Use the <NEXT> or <PREV> key to select one of the 
options described in Table 8-5.
5. Press <ENTER>. The function you chose in Step 4 exe-
cutes.
WalkTest
WalkTest allows one person to test the functionality of the 
panel’s devices. Once the panel is placed into WalkTest 
mode, you can test the following:
• Initiating Device Alarm Sensing. To test each detector’s 
alarm capability, use a pole magnet or canned smoke to 
activate the initiating device. If the device is functioning 
correctly, one of two things happen:
- If the WalkTest signaling option is set to SIG, the 
panel pulses the device’s zone number on the 
panel’s NACs. After 15 seconds the panel drops 
power to the zone, resetting the activated device. 
Subsequently activating another initiating device 
on the same zone sounds a double pulse on the 
NAC.
- If the WalkTest signaling option is set to SIL, the 
panel logs the alarm activation to the ALOG (alarm 
log). Use the History Logs menu option to view the 
ALOG. Use the Reports menu option to print a 
copy of the ALOG.
• Initiating Device Trouble Sensing. To test the panel’s 
ability to sense a trouble condition for each initiating 
device, disconnect one of the IDC wires at the detector. 
If the panel senses the trouble condition correctly, one 
of two things happen:
- If the WalkTest signaling option is set to SIG, the 
panel activates the panel’s NACs for four seconds. 
- If the WalkTest signaling option is set to SIL, the 
panel logs the trouble in the TLOG (trouble log). 
Use the History Logs menu option to view the 
TLOG. Use the Reports menu option to print a copy 
of the TLOG.
• Earth Ground Sensing. To test the panel’s ability to 
detect an Earth Ground, short one of the panel’s circuits 
to Earth. If the panel senses the trouble condition cor-
rectly, one of two things happen:
- If the WalkTest signaling option is set to SIG, the 
panel activates the panel’s NACs for four seconds. 
- If the WalkTest signaling option is set to SIL, the 
panel logs the trouble in the TLOG (trouble log). 
Use the History Logs menu option to view the 
TLOG. Use the Reports menu option to print a copy 
of the TLOG.
• NAC Trouble Sensing. To test the panel’s ability to 
sense a trouble condition for each NAC, disconnect one 
of the NAC wires at the panel. If the panel senses the 
trouble condition correctly, one of two things happen:
- If the WalkTest signaling option is set to SIG, the 
panel activates the panel’s NACs for four seconds. 
- If the WalkTest signaling option is set to SIL, the 
panel logs the trouble in the TLOG (trouble log). 
Use the History Logs menu option to view the 
TLOG. Use the Reports menu option to print a copy 
of the TLOG.
Setting WalkTest Options
WalkTest options are set via the WalkTest entry at the main 
menu. You must be logged in at either Access Level 3 or 4 to 
set the WalkTest options.
Table 8-5  Diagnostic Options
Option Description
BAT CHGR 
METER
View battery charger incoming voltage, 
and output current.
Battery Meter View battery voltage and battery load
HW Reset
The Hardware Reset is context sen-
sitive. If the reset is performed with 
an alarm in the system, the alarms 
are allowed to reset. If there are no 
alarms present, a HW reset (power 
is dropped to all zones for 15 sec-
onds) is performed. The hardware 
reset will attempt to clear any 
latched troubles. 
CLR Tally/TBL
This option clears the alarm verifica-
tion tallies for all IDCs in the system. 
Typically this is only done when an 
Alarm Verification Tally Limit trouble 
occurs. The Alarm Verification Tally 
Limit trouble occurs if an IDC pro-
grammed for alarm verification starts 
the verification cycle, but does not 
verify 10 times.
Technical Manuals Online! - http://www.tech-man.com